Customer Data: |
 |
|
Signed downtown customers |
97 |
FY 2007 Energy Sales |
35,652,212 ton-hours |
Building Area Served: |
|
Downtown |
18.8 million sq. ft. |
Chilled Water Sources: |
|
Main plant, 76 West Kellogg Boulevard |
|
Six electric chillers |
12,737 tons |
Two absorption chillers |
1,000 tons |
New Plant, 10th and Sibley |
|
Two electric chiller |
4,500 tons |
Chilled water storage systems |
10,800 tons |
Satellite chillers |
3,900 tons |
Total |
32,937 tons |
Piping: |
|
Type |
steel pipe wrapped in protective coating with cathodic protection |
Diameter |
3-inch to 30-inch |
Length |
25,300 feet each, supply and return |
Volume of distribution system |
975,000 gallons |
Volume of storage system |
6,700,000 gallons |
Operating Data: |
|
Temperature |
|
Supply |
42 degrees F |
Return |
56 degrees F |
Pressure |
|
Supply |
150 psi |
Minimum pressure differential |
15 psi |
Reliability: |
|
Reliability rate |
99.99% |
|