Customer Data
|
 |
|
Signed downtown customers:
|
 |
98
|
 |
|
FY 2009 Energy Sales:
|
 |
34,605,266 ton-hours
|
 |
|
Building Area Served:
|
 |
19.3 million sq. ft.
|
 |
Chilled Water Sources
|
 |
|
Main plant, 76 West Kellogg Boulevard
|
|
Six electric chillers:
|
 |
12,737 tons
|
|
Two absorption chillers:
|
 |
1,000 tons
|
 |
|
New Plant, 10th and Sibley
|
|
Two electric chillers:
|
 |
4,500 tons
|
|
Chilled water storage systems:
|
 |
10,800 tons
|
|
Satellite chillers:
|
 |
3,900 tons
|
 |
|
Total:
|
 |
32,937 tons
|
 |
Piping
|
 |
|
Type:
|
 |
steel pipe wrapped in protective coating with cathodic protection
|
 |
|
Diameter:
|
 |
3-inch to 30-inch
|
 |
|
Length:
|
 |
35,600 feet each, supply and return
|
 |
|
Volume of distribution system:
|
 |
980,000 gallons
|
 |
|
Volume of storage system:
|
 |
6,700,000 gallons
|
 |
Operating Data
|
 |
|
Supply Temperature:
|
 |
42 degrees F
|
 |
|
Return Temperature:
|
 |
56 degrees F
|
 |
|
Supply Pressure:
|
 |
150 psi
|
 |
|
Minimum pressure differential:
|
 |
15 psi
|
 |
|
Reliability rate:
|
 |
99.997%
|
 |