Customer Data
|
 |
|
Signed customer buildings:
|
 |
187
|
 |
|
Mount Airy homes:
|
 |
298
|
 |
|
FY 2010 energy sales:
|
 |
343,871 MWh
|
 |
|
Total Building Area Served:
|
 |
31.7 million sq. ft.
|
 |
Heat Sources
|
 |
|
Main plant, 76 West Kellogg Boulevard
|
|
Two coal/gas-fired boilers:
|
 |
88 MW
|
|
Four gas/oil-fired boilers:
|
 |
106 MW
|
|
Combined heat and power plant:
|
 |
65 MW
|
 |
|
Regions Hospital plant
|
|
Four gas/oil-fired boilers:
|
 |
25 MW
|
|
Mobile boiler (temporary and/or backup):
|
 |
5 MW
|
 |
|
Total:
|
 |
289 MW
|
 |
Piping
|
 |
|
Type:
|
 |
prefabricated steel pipe with polyurethane insulation encased in polyethylene jacket
|
 |
|
Diameter:
|
 |
3/4-inch to 28-inch
|
 |
|
Length:
|
 |
105,200 feet each, supply and return
|
 |
|
Volume:
|
 |
915,000 gallons
|
 |
Operating Data
|
 |
|
Supply Temperature:
|
 |
190-250 degrees F
|
 |
|
Return Temperature:
|
 |
140-160 degrees F
|
 |
|
Supply Pressure:
|
 |
180 psi
|
 |
|
Minimum pressure differential:
|
 |
20 psi
|
 |
|
Reliability rate:
|
 |
99.997%
|
 |